49 CFR § 192.477 Transportation of Natural and Other Gas by Pipeline: Minimum Federal Safety Standards

§ 192.477 Internal corrosion control: Monitoring.

Current through Sep 25, 2026 · Read all of Part 192

⚠ 31 pending changes to Part 192

If corrosive gas is being transported, coupons or other suitable means must be used to determine the effectiveness of the steps taken to minimize internal corrosion. Each coupon or other means of monitoring internal corrosion must be checked two times each calendar year, but with intervals not exceeding 7 1/2 months.

[Amdt. 192-33, 43 FR 39390, Sept. 5, 1978]

← § 192.476 Internal corrosion control: Design and construction of transmission line.§ 192.478 [Reserved] →