49 CFR § 192.365 Transportation of Natural and Other Gas by Pipeline: Minimum Federal Safety Standards

§ 192.365 Service lines: Location of valves.

Current through Sep 25, 2026 · Read all of Part 192

⚠ 31 pending changes to Part 192

(a) Relation to regulator or meter. Each service-line valve must be installed upstream of the regulator or, if there is no regulator, upstream of the meter.

(b) Outside valves. Each service line must have a shut-off valve in a readily accessible location that, if feasible, is outside of the building.

(c) Underground valves. Each underground service-line valve must be located in a covered durable curb box or standpipe that allows ready operation of the valve and is supported independently of the service lines.

← § 192.363 Service lines: Valve requirements.§ 192.367 Service lines: General requirements for connections to main piping. →