49 CFR § 192.353 Transportation of Natural and Other Gas by Pipeline: Minimum Federal Safety Standards

§ 192.353 Customer meters and regulators: Location.

Current through Sep 25, 2026 · Read all of Part 192

⚠ 31 pending changes to Part 192

(a) Each meter and service regulator, whether inside or outside a building, must be installed in a readily accessible location and be protected from corrosion and other damage, including, if installed outside a building, vehicular damage that may be anticipated. However, the upstream regulator in a series may be buried.

(b) Each service regulator installed within a building must be located as near as practical to the point of service line entrance.

(c) Each meter installed within a building must be located in a ventilated place and not less than 3 feet (914 millimeters) from any source of ignition or any source of heat which might damage the meter.

(d) Where feasible, the upstream regulator in a series must be located outside the building, unless it is located in a separate metering or regulating building.

[35 FR 13257, Aug. 19, 1970, as amended by Amdt. 192-85, 63 FR 37503, July 13, 1998; Amdt. 192-93, 68 FR 53900, Sept. 15, 2003]

← § 192.351 Scope.§ 192.355 Customer meters and regulators: Protection from damage. →