40 CFR § 141.552 National Primary Drinking Water Regulations

§ 141.552 My system consists of “alternative filtration” and is required to conduct a demonstration—what is required of my system and how does the State establish my turbidity limits?

Current through Aug 22, 2025 · Read all of Part 141

(a) If your system consists of alternative filtration(filtration other than slow sand filtration, diatomaceous earth filtration, conventional filtration, or direct filtration) you are required to conduct a demonstration (see tables in § 141.551). Your system must demonstrate to the State, using pilot plant studies or other means, that your system's filtration, in combination with disinfection treatment, consistently achieves:

(1) 99 percent removal of Cryptosporidium oocysts;

(2) 99.9 percent removal and/or inactivation of Giardia lamblia cysts; and

(3) 99.99 percent removal and/or inactivation of viruses.

(b) [Reserved]