30 CFR § 77.314 Mandatory Safety Standards, Surface Coal Mines and Surface Work Areas of Underground Coal Mines

§ 77.314 Automatic temperature control instruments.

Current through Jul 27, 2026 · Read all of Part 77

(a) Automatic temperature control instruments for thermal dryer system shall be of the recording type.

(b) Automatic temperature control instruments shall be locked or sealed to prevent tampering or unauthorized adjustment. These instruments shall not be set above the maximum allowable operating temperature.

(c) All dryer control instruments shall be inspected and calibrated at least once every 3 months and a record or certificate of accuracy, signed by a trained employee or by a servicing agent, shall be kept at the plant.

← § 77.313 Wet-coal feedbins; low-level indicators.§ 77.315 Thermal dryers; examination and inspection. →